NFPA 61 or NFPA 68 Combustible Dust Explosion Protection of Industrial Bucket Elevators

By Payton Ball, BSME, Regional Sales Manager, REMBE® Inc.

Let’s say you are a Project Engineer for a pet food production facility.  You’ve recently hired a consultant to conduct a Dust Hazard Analysis (DHA), according to NFPA 61, Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food Processing Facilities, rev. 2020 (NFPA 61) & NFPA 652, Standard on the Fundamentals of Combustible Dust, rev.2019 (NFPA 652). You are now tasked with the responsibility of implementing several DHA recommendations, one of which is to implement explosion protection on your plant’s bucket elevators in compliance with the NFPA standards.

Bucket elevators provide you a means to transport large volumes     of product via belt/chain efficiently and to higher elevations than typically practical with pneumatic or open belt conveying.  These systems in your plant are essential, and transport everything from whole grains, to processed additives and ingredients.  Your challenge is to correctly interpret and apply the applicable NFPA standards.  While your facility falls under the NFPA 61 umbrella for food processing facilities, NFPA 68, Standard on Explosion Protection by Deflagration Venting, rev. 2018 (NFPA 68), the standard for deflagration venting, may also apply.

Many questions arise in food processing facilities with respect to bucket elevator explosion protection. Prescriptive methods of explosion protection for bucket elevators can be found in both NFPA 68 and NFPA 61 Standards.  NFPA 68 lays out parameters for the protection of all hazardous dusts, while the methodology in NFPA 61 is specifically for grain handling. In many cases the specific commodity NFPA standards refer to the other core combustible dust standards.

Determining the applicable standard to use for bucket elevator protection is rather simple! It starts and stops with the definition of “bulk raw grain”.  In NFPA 61-20 3.3.6, bulk raw grain is defined as “Grain materials, such as cereal grains, oilseeds, and legumes, that have not undergone processing or size reduction”.  The key characteristic here is regarding processing, and size reduction.  We look further in the NFPA Standard 61 to find two primary divisions for bucket elevator legs: “Section 9.3.14.2 – Legs Handling Bulk Raw Grain” and “Section 9.3.14.3 “Legs handling materials other than Bulk Raw Grain That Present an Explosion Hazard.”. The former provides the prescriptive step-by-step methodology for elevator leg explosion venting. The latter  clearly states: “9.3.14.3.3* Legs or portions of legs that are located inside shall have the maximum practicable explosion relief area directly to the outside, a flame-arresting and particulate retention vent system in accordance with NFPA 68, or explosion suppression in accordance with NFPA 69.” This means that other than the handling of your whole grains, NFPA 68 protection methodology must be used for indoor elevators!

After making that distinction, the prescriptive solution is like a recipe.  Each characteristic of your bucket elevator and dust characteristics play a role.  The determinations are demonstrated in the decision matrix to the right.

Many processing facilities and elevator manufacturers prefer to utilize NFPA 61 wherever possible.  The method is simple, and typically requires fewer explosion panels than NFPA 68 which lowers cost.  As is true with most industry safety measures, less expensive is not always adequate.

Why differentiate bulk raw grain from dust after processing and size reduction?  The simple answer is that the severity of an event can vary drastically with change in dust size, and moisture content.

The dust that is present when handling bulk raw grain presents an explosion hazard, but not bulk raw grain itself.  Prior to processing, the dust concentration in the elevator legs is often very low with elevated moisture content, making the probability and severity of an explosion less than when handling the same ground/milled/ crushed/dried product at a different stage of processing.

In most processing facilities, the material undergoes multiple changes before the end of the process.  This can be as simple as milling, or as complex as chemical processing.  Either way, once a bulk raw grain is processed, NFPA 61 is no longer the approved method for indoor bucket elevator explosion vent sizing, and NFPA 68 must be followed for adequate protection and compliance.

After processing, the product often no longer contains larger chunks, and contains a greater concentration of dust particles.  Bucket elevator explosion venting design methodology per NFPA 68 takes into consideration the Kst, of the material, and strength of the elevator to reflect the real-life/worst case scenario.  This becomes crucial in the sizing of explosion vents for bucket elevators.

A critical point to keep in mind as you review all bucket elevators in your facility: Just because one elevator qualifies for the NFPA 61 approach, DOES NOT mean that all bucket elevators in that plant can utilize the same methodology if the process/media/material is different!  Each elevator must be evaluated on a case-by-case basis. It may also be worth considering future process changes and design for the anticipated worst case scenario.

A few additional considerations:

  • Bucket elevators located indoors cannot be explosion vented to the interior space. It might be possible to direct bucket elevator vents through an exterior wall with short vent ducts; however, the ducts must be accounted for in the venting design and casing strength according to NFPA 68. This is more often not feasible due to elevator distances to exterior walls, so alternate safe indoor protection such as flameless venting or chemical suppression must be used. The Q-box II and the new Q-Ball-E by REMBE® are certified and NFPA 68 compliant flame arresting and particulate retention devices when installed on interior elevators provide a reliable, maintenance free explosion protection solution.
  • To complement explosion protection, the inlet and outlet of the elevator must be isolated to prevent the propagation of a fireball into adjacent areas or equipment. Passive protection solutions can be accomplished with NFPA 69 compliant rotary air lock valves for example. For active chemical suppression explosion protection solutions, additional suppressant bottles are installed on the in and out feed chutes in addition to the casing that trigger with the detection of spark or pressure rise.
  • It is important to be aware of additional bucket elevator design and performance requirements for all food handling materials that together serve as fire and explosion preventative measures. These specific preventative requirements are outlined in NFPA 61 Section 9.3.14.1 and include but are not limited to, drive safety requirements, inspection access, operational monitors and sensors

When evaluating explosion protection for bucket elevators, answer the one overarching question:  Is this a bulk raw grain process within the definition of NFPA Standard 61 section 9.3.14.3.1 or not?  This is your guide to safe and compliant explosion protection for your facility and employees.

Contact Payton Ball for more information about protecting elevators or combustible dust explosion protection:

Payton Ball, BSME

Sales Engineer

REMBE® Inc.

PBa@rembe.us

704.716.7022

About REMBE®:

For over 45 years, REMBE® has been and continues to be a leader in the innovation and manufacture of high‐quality explosion protection systems, process safety systems and dynamic weighing systems.  As the inventor of flameless venting, REMBE® specializes in combustible dust explosion prevention/protection systems for many applications across a multitude of industries. REMBE® has led the process safety industry in new, more adaptable rupture disc products to address ever‐changing, complex needs.  And the C‐LEVER dynamic weighing system provides a reliable, easy‐to-use-and-maintain option for continuous weighing.

REMBE® Inc., located in Fort Mill, SC, serves the North American market and is ready to assist you. Visit our website www.rembe.us, email us info@rembe.us or call 704.716.7022 for more information.

Share on Socials!

Related Articles

Related Articles

Do N95 masks really blow coronavirus into the air? What to know about the viral post

Maybe you’ve seen it — a post on Facebook challenging the effectiveness of masks to combat coronavirus, according to the Raleigh News & Observer. It’s said ...
Read More

UVA parent reports mold-infested dorm

Jamie Scher says she was moving her son, a second-year University of Virginia student, into his dorm over the Labor Day weekend when she discovered the ...
Read More

START-UP-ZONE FOR NEWCOMERS AT A+A 2021

A+A 2021, International Trade Fair with Congress for Safety, Security and Health at Work, will support national and international newcomers with the START-UP ZONE. This segment ...
Read More